Bethel parks committee to discuss a $1 fitness center fix projected to save $46,000 a year

by Cale Green · draft by Maggie AlaskaNews(1w ago)
2 min readBethel, Alaska

Bethel's Community Parks and Recreation Committee on Monday will discuss an energy audit that found the YK Fitness Center could save nearly $46,000 a year by changing when and how its ventilation system runs.

The building runs its ventilation as if it were occupied even when it's closed, according to the audit by Christian Webb of the Alaska Native Tribal Health Consortium. A coil meant to recover heat from exhaust air is also underused. The center is open 5:30 am to 9 pm every day but Thursday.

Webb recommends setting the ventilation schedule on the building's control computer to match actual open hours, and raising the heat-recovery setpoint to 70 or 75 degrees so more heat is pulled from the damp pool-room exhaust and the boilers burn less fuel. The audit lists the cost at $1, because its software won't accept zero.

A second $1 change, turning the heat down to 65 degrees in the lobby, locker rooms and exercise rooms when the building is closed, would save about $4,000 more.

The audit puts energy costs at the 25,741-square-foot center, built in 2014, at about $419,000 a year, about 83% of it for heating oil. All of the audit's recommendations together would cut that bill by about $51,000 a year, or 12.2%, for about $36,000.

The item, led by committee member Sean Glasheen, is up for discussion, not a vote. The meeting starts at 6 pm at 300 Chief Eddie Hoffman Highway and on Zoom, and written comments are due by 4 pm Monday.